Multi Core Power Cables

( NYY , N2XY , N2XH , NAYY , NA2XY , NA2XH )

Layers Construction

  • Cu / PVC / PVC
  • Cu / XLPE / PVC
  • Cu / XLPE / PE
  • Cu / XLPE / LSZH
  • Al / PVC / PVC
  • Al / XLPE / PVC
  • Al / XLPE / PE
  • Al / XLPE/ LSZH

Multi Core copper and aluminum power control cables with PVC or XLPE insulation and PVC or PE or LSZH coating

Cable Structure

Conductor type and class:

Copper conductor according to IEC 60228 ( ISIRI 3084 ), class 1 ( solid ), class 2 ( stranded ) or class 5 ( flexible )

PVC core insulation:

Compound type of PVC / A or XLPE Compound

Core insulation colors:

According to customer request

Inner sheath material:

For round sections in the form of extruded PVC coating and for sector sections in the form of polypropylene ( PP ) strips.

Outer sheath material:

Compound type of PVC / ST1 , ST2 or HDPE Compound or LSZH Compound

Sheath color:

According to customer request

Technical Data

Temperature range:

PVC insulation: -30 ℃ to +70 ℃
XLPE insulation: -40 ℃ to +90 ℃

Nominal Voltage Uo / U:

0/6 / 1 kV

Reference Standard:

INSO 3569 – 1
IEC 60502 – 1

Wire code:

NYY – O
NYY – J
N2XY
N2X2Y
N2XH
NAYY – O
NAYY – J
NA2XY
NA2X2Y
NA2XH

Application

These types of cables are used for fixed installation in the basement, inside the ducts, in electrical substations, facilities inside the building and in the open space where there is no possibility of mechanical damage to the cable. In places where there is a possibility of fire, LSZH materials are used to prevent the release of toxic gases and corrosive gases.

Properties

Multi-core copper power cables with PVC insulation and coating

Approx.
Weight

( kg / km )
Max. Conductors
Resistance at 20˚C
( Ω / km )
Average
Outer Diameter
( mm )
Nominal Sheath
Thickness
( mm )
Nominal Filler
Thickness
( mm )
Nominal Insulation
Thickness
( mm )
Nominal Cross
Section of Conductors
( mm)
182 12.1 11.6 1.8 1 0.8 2×1.5
220 7.41 12.4 1.8 1 0.8 2×2.5
297 4.61 14.1 1.8 1 1 2×4
365 3.08 15.1 1.8 1 1 2×6
489 1.83 16.7 1.8 1 1 2×10
705 1.15 19.8 1.8 1 1 2×16
1022 0.727 23.2 1.8 1 1.2 2×25
1300 0.524 25.5 1.8 1 1.2 2×35
205 12.1 12 1.8 1 0.8 3×1.5
253 7.41 12.9 1.8 1 0.8 3×2.5
348 4.61 14.7 1.8 1 1 3×4
435 3.08 15.9 1.8 1 1 3×6
596 1.83 17.6 1.8 1 1 3×10
868 1.15 20.9 1.8 1 1 3×16
1274 0.727 24.6 1.8 1 1.2 3×25
1638 0.524 27.1 1.8 1 1.2 3×35
236 12.1 12.8 1.8 1 0.8 4×1.5
297 7.41 13.8 1.8 1 0.8 4×2.5
412 4.61 15.8 1.8 1 1 4×4
522 3.08 17.1 1.8 1 1 4×6
726 1.83 19.1 1.8 1 1 4×10
1065 1.15 22.7 1.8 1 1 4×16
1574 0.727 26.9 1.8 1 1.2 4×25
2038 0.524 29.6 1.8 1 1.2 4×35
270 12.1 13.7 1.8 1 0.8 5×1.5
342 7.41 14.7 1.8 1 0.8 5×2.5
480 4.61 17.1 1.8 1 1 5×4
613 3.08 18.5 1.8 1 1 5×6
861 1.83 20.6 1.8 1 1 5×10
1269 1.15 24.8 1.8 1 1 5×16
1885 0.727 29.4 1.8 1 1.2 5×25
2466 0.524 32.7 1.8 1 1.2 5×35
1434 0.727/1.15 24.5 1.8 1 1.2/1 3×25 + 16
1795 0.524/1.15 26.9 1.8 1 1.2/1 3×35 + 16
2069 0.387/0.727 27.6 1.9 0.4 1.4/1.2 3×50 + 25
2824 0.268/0.524 30.6 2 0.4 1.4/1.2 3×70 + 35
3876 0.193/0.387 35.4 2.2 0.4 1.6/1.4 3×95 + 50
4850 0.153/0.268 38.2 2.3 0.4 1.6/1.4 3×120 + 70
7334 0.124/0.268 42.2 2.4 0.4 1.8/1.4 3×150 + 70
8523 0.0991/0.193 46.6 2.6 0.4 2/1.6 3×180 + 95
9478 0.0762/0.153 52.6 2.8 0.4 2.2/1.6 3×240 + 120

Multi-core copper power cables with XLPE insulation and PVC or PE sheath

Approx.
Weight

( kg / km )
Max. Conductors
Resistance at 20˚C
( Ω / km )
Average
Outer Diameter
( mm )
Nominal Sheath
Thickness
( mm )
Nominal Filler
Thickness
( mm )
Nominal Insulation
Thickness
( mm )
Nominal Cross
Section of Conductors
( mm)
166 12.1 11.2 1.8 1 0.7 2×1.5
203 7.41 12 1.8 1 0.7 2×2.5
252 4.61 12.9 1.8 1 0.7 2×4
315 3.08 13.9 1.8 1 0.7 2×6
433 1.83 15.5 1.8 1 0.7 2×10
636 1.15 18.6 1.8 1 0.7 2×16
934 0.727 22 1.8 1 0.9 2×25
1202 0.524 24.3 1.8 1 0.9 2×35
186 12.1 11.6 1.8 1 0.7 3×1.5
232 7.41 12.5 1.8 1 0.7 3×2.5
294 4.61 13.4 1.8 1 0.7 3×4
376 3.08 14.6 1.8 1 0.7 3×6
530 1.83 16.3 1.8 1 0.7 3×10
787 1.15 19.6 1.8 1 0.7 3×16
1168 0.727 23.3 1.8 1 0.9 3×25
1521 0.524 25.8 1.8 1 0.9 3×35
213 12.1 12.1 1.8 1 0.7 4×1.5
270 7.41 13.3 1.8 1 0.7 4×2.5
348 4.61 14.4 1.8 1 0.7 4×4
452 3.08 15.6 1.8 1 0.7 4×6
646 1.83 17.6 1.8 1 0.7 4×10
965 1.15 21.3 1.8 1 0.7 4×16
1445 0.727 25.4 1.8 1 0.9 4×25
1894 0.524 28.2 1.8 1 0.9 4×35
242 12.1 13.1 1.8 1 0.7 5×1.5
311 7.41 14.2 1.8 1 0.7 5×2.5
405 4.61 15.4 1.8 1 0.7 5×4
530 3.08 16.8 1.8 1 0.7 5×6
766 1.83 19 1.8 1 0.7 5×10
1151 1.15 23.2 1.8 1 0.7 5×16
1731 0.727 27.8 1.8 1 0.9 5×25
2277 0.524 30.9 1.8 1 0.9 5×35
1310 0.727/1.15 23.2 1.8 1 0.9/0.7 3×25 + 16
1659 0.524/1.15 25.6 1.8 1 0.9/0.7 3×35 + 16
2324 0.387/0.727 27.4 1.9 0.4 1/0.9 3×50 + 25
3157 0.268/0.524 31 1.9 0.4 1.1/0.9 3×70 + 35
4226 0.193/0.387 35.4 2.1 0.4 1.1/1 3×95 + 50
5285 0.153/0.268 38.4 2.2 0.4 1.2/1.1 3×120 + 70
6403 0.124/0.268 42.8 2.3 0.4 1.4/1.1 3×150 + 70
7943 0.0991/0.193 47.2 2.5 0.4 1.6/1.1 3×180 + 95
10194 0.0601/0.153 53.4 2.7 0.4 1.7/1.2 3×240 + 120

These cables can be produced with LSZH coating as well as fire resistant cables.

Aluminum multi-core power cables with PVC insulation and coating

Approx.
Weight

( kg / km )
Max. Conductors
Resistance at 20˚C
( Ω / km )
Average
Outer Diameter
( mm )
Nominal Sheath
Thickness
( mm )
Nominal Filler
Thickness
( mm )
Nominal Insulation
Thickness
( mm )
Nominal Cross
Section of Conductors
( mm)
388 3.08 17.4 1.8 1 1 2×10
531 1.91 19.9 1.8 1 1 2×16
768 1.2 23.8 1.8 1 1.2 2×25
839 0.868 25.2 1.8 1 1.2 2×35
431 3.08 18.4 1.8 1 1 3×10
554 1.91 20.6 1.8 1 1 3×16
776 1.2 24.3 1.8 1 1.2 3×25
949 0.868 26.7 1.8 1 1.2 3×35
482 3.08 19.1 1.8 1 1 4×10
687 1.91 22.9 1.8 1 1 4×16
913 1.2 26.6 1.8 1 1.2 4×25
1118 0.868 29.2 1.8 1 1.2 4×35
573 3.08 21.6 1.8 1 1 5×10
746 1.91 24.5 1.8 1 1 5×16
1166 1.2 30.2 1.8 1 1.2 5×25
1316 0.868 32.2 1.9 1 1.2 5×35
899 1.2/1.91 26.2 1.8 1 1.2/1 3×25 + 16
1061 0.868/1.91 28 1.8 1 1.2/1 3×35 + 16
1024 0.641/1.2 28.1 1.9 0.4 1.4/1.2 3×50 + 25
1363 0.433/0.868 32.1 2 0.4 1.4/1.2 3×70 + 35
1779 0.32/0.641 38.3 2.2 0.4 1.6/1.2 3×95 + 50
2235 0.253/0.443 42.1 2.3 0.4 1.6/1.4 3×120 + 70
2535 0.206/0.443 44.5 2.4 0.4 1.8/1.4 3×150 + 70
3175 0.164/0.320 48.2 2.6 0.4 2/1.6 3×180 + 95
4085 0.125/0.253 60.3 2.8 0.4 2.2/1.6 3×240 + 120

Aluminum multi-core power cables with XLPE insulation and PVC or PE sheath

Approx.
Weight

( kg / km )
Max. Conductors
Resistance at 20˚C
( Ω / km )
Average
Outer Diameter
( mm )
Nominal Sheath
Thickness
( mm )
Nominal Filler
Thickness
( mm )
Nominal Insulation
Thickness
( mm )
Nominal Cross
Section of Conductors
( mm)
328 3.08 16.2 1.8 1 0.7 2×10
427 1.91 18.4 1.8 1 0.7 2×16
604 1.2 21.8 1.8 1 0.9 2×25
742 0.868 24 1.8 1 0.9 2×35
361 3.08 17.1 1.8 1 0.7 3×10
474 1.91 19.4 1.8 1 0.7 3×16
673 1.2 23 1.8 1 0.9 3×25
832 0.868 25.4 1.8 1 0.9 3×35
413 3.08 18.4 1.8 1 0.7 4×10
548 1.91 21 1.8 1 0.7 4×16
785 1.2 25.1 1.8 1 0.9 4×25
976 0.868 27.8 1.8 1 0.9 4×35
472 3.08 20 1.8 1 0.7 5×10
629 1.91 22.8 1.8 1 0.7 5×16
906 1.2 27.4 1.8 1 0.9 5×25
1131 0.868 30.4 1.9 1 0.9 5×35
727 1.2/1.91 23 1.8 1 0.9/0.7 3×16 + 25
886 0.868/1.91 25.4 1.8 1 0.9/0.7 3×16 + 35
861 0.641/1.2 26.6 1.9 0.4 1/0.9 3×25 + 50
1134 0.443/0.868 29.8 2 0.4 1.1/0.9 3×35 + 70
1488 0.32/0.641 34.2 2.2 0.4 1.1/1 3×50 + 95
1841 0.253/0.443 37.2 2.3 0.4 1.2/1.1 3×70 + 120
2222 0.206/0.443 41.2 2.4 0.4 1.4/1.1 3×70 + 150
2756 0.164/0.320 45.6 2.6 0.4 1.6/1.1 3×95 + 180
3484 0.125/0.253 51.4 2.8 0.4 1.7/1.2 3×120 + 240