Screened , Flexible, Control Cables
( H05VC4V - F , NYSLCY , NYSLYCY )
Layers Construction
- Cu / PVC / Bd / CWB / PVC
- Cu / PVC / PET / CWB / PVC
Flexible screened control cables, PVC insulated, PVC inner sheath, braided copper wire for electromagnetic protection, PVC sheathed.
Cable Structure
Conductor type and class:
Flexible copper conductor according to IEC 60228 ( ISIRI 3084 ), class 5
PVC core insulation:
Compound type of PVC / D
Core insulation colors:
Up to 5 cores, color or number coding and for more than 5 cores, number coded imprints. For 3 or more cores, the green / yellow earth core is the last core in the outer layer.
PVC inner covering:
Compound type of PVC/ ST 5.( The inner covering can be substituted by a polyester film if customer requests )
Screen:
Braided copper or tinned copper wire.
PVC outer sheath:
Compound type of PVC/ ST5 *
* This type of PVC compound is not oil resistant.
Sheath color:
Gray
Technical Data
Temperature range:
-30 ℃ to +70 ℃
Nominal Voltage Uo / U:
300 / 500 V
Reference Standard:
ISIRI 607 – 5
IEC 60227 – 5
Wire code:
ISIRI ( 607 ) 74
60227 IEC 74
H05VC4V – F
NYSLCY
NYSLYCY
Application
These types of cables are used as link and connection control cables for machine tools, conveyor belts and plant production lines, measuring and automatic control, computer units, construction equipments, power stations, cooling and data processing systems and office machines. They are mostly installed in dry, damp or wet rooms at normal stresses.
The copper braid serves as electromagnetic screen between the internal electric circuits and the environment, therefore, it would eliminate any effects of electrical noises in the system.
Properties
Approx. Weight ( kg / km ) | Max. Conductors Resistance at 20˚C ( Ω / km ) | Average Outer Diameter ( mm ) | Nominal Sheath Thickness ( mm ) | Nominal Diameter of Screen Conductor ( mm ) | Nominal Inner Covering Thickness ( mm ) | Nominal Insulation Thickness ( mm ) | No. & Nominal Cross Section of Conductors ( mm2 ) | |
Max. | Min. | |||||||
70 | 39 | 9.6 | 7.7 | 0.9 | 0.15 | 0.7 | 0.6 | 2×0.5 |
80 | 26 | 10 | 8 | 0.9 | 0.15 | 0.7 | 0.6 | 2×0.75 |
82 | 19.5 | 10.3 | 8.2 | 0.9 | 0.15 | 0.7 | 0.6 | 2×1 |
104 | 13.3 | 11.6 | 9.3 | 1 | 0.15 | 0.7 | 0.7 | 2×1.5 |
141 | 7.98 | 13.3 | 10.7 | 1.1 | 0.15 | 0.7 | 0.8 | 2×2.5 |
75 | 39 | 10 | 8 | 0.9 | 0.15 | 0.7 | 0.6 | 3×0.5 |
89 | 26 | 10.4 | 8.3 | 0.9 | 0.15 | 0.7 | 0.6 | 3×0.75 |
97 | 19.5 | 11 | 8.8 | 1 | 0.15 | 0.7 | 0.6 | 3×1 |
127 | 13.3 | 12.1 | 9.7 | 1 | 0.15 | 0.7 | 0.7 | 3×1.5 |
177 | 7.98 | 14 | 11.3 | 1.1 | 0.15 | 0.7 | 0.8 | 3×2.5 |
91 | 39 | 10.7 | 8.5 | 0.9 | 0.15 | 0.7 | 0.6 | 4×0.5 |
106 | 26 | 11.3 | 9.1 | 1 | 0.15 | 0.7 | 0.6 | 4×0.75 |
116 | 19.5 | 11.7 | 9.4 | 1 | 0.15 | 0.7 | 0.6 | 4×1 |
157 | 13.3 | 13.2 | 10.7 | 1.1 | 0.15 | 0.7 | 0.7 | 4×1.5 |
221 | 7.98 | 15.5 | 12.6 | 1.2 | 0.15 | 0.8 | 0.8 | 4×2.5 |
105 | 39 | 11.6 | 9.3 | 1 | 0.15 | 0.7 | 0.6 | 5×0.5 |
122 | 26 | 12.1 | 9.7 | 1 | 0.15 | 0.7 | 0.6 | 5×0.75 |
141 | 19.5 | 12.8 | 10.3 | 1.1 | 0.15 | 0.7 | 0.6 | 5×1 |
189 | 13.3 | 14.7 | 11.8 | 1.2 | 0.15 | 0.8 | 0.7 | 5×1.5 |
276 | 7.98 | 17.2 | 13.9 | 1.3 | 0.2 | 0.8 | 0.8 | 5×2.5 |
118 | 39 | 12.4 | 9.9 | 1 | 0.15 | 0.7 | 0.6 | 6×0.5 |
143 | 26 | 13.1 | 10.5 | 1.1 | 0.15 | 0.7 | 0.6 | 6×0.75 |
162 | 19.5 | 13.6 | 11 | 1.1 | 0.15 | 0.7 | 0.6 | 6×1 |
217 | 13.3 | 15.7 | 12.7 | 1.2 | 0.15 | 0.8 | 0.7 | 6×1.5 |
325 | 7.98 | 18.7 | 15.2 | 1.4 | 0.2 | 0.8 | 0.8 | 6×2.5 |
Note: For all sizes, the minimum insulation resistance at 70 degrees Celsius and 500 volts is more than 0.013 MΩ.km.